Intermediate

Checking Strut Channel Support Reactions

Separate the channel check from fittings, rods and anchors. Use the example below to practice the review and record an output that another reviewer can reproduce.

Inputs and Prerequisites

Channel series, hanger spacing, threaded rod layout and accessory load documentation.

Review Workflow

  1. Attached load
  2. Channel
  3. Hangers
  4. Substrate
  1. Separate the channel check from fittings, rods and anchors.
  2. Locate points of load application and potential torsion.
  3. Check simple equilibrium before comparing ratings.

Worked Example

A centered assumed load of 1.2 kN on a 1.5 m simply supported channel gives 0.6 kN at each hanger. If the bracket applies the same load 100 mm away from the channel axis it introduces another 0.12 kN·m about that axis.

Output Checks and Common Errors

Check table orientation, deflection basis, fitting configuration and substrate separately.

Official References